260
MY HOME
WIRING DIAGRAMS
Energy management
4 zone villa
DIAGRAM DESCRIPTION
This diagram represents an example
of a heating and cooling system
made with Climaveneta unit and
Combination boiler.
By means of the TiThermo software
the 99 zone control unit item 3550
can be programmed to use the
reading of the outside temperature
from the Climaveneta system to
manage systems with combination
boilers.
Depending on the outside
temperature the control unit
activates the most suitable and
convenient heating system
depending on the heat yield.
During the spring and autumn
rooms can be heated using the heat
generated by the Chiller. This heat is
however not suf cient in the winter
when a Combination boiler, generally
supplied by gas, must be used.
The MY HOME temperature control
system switches between the
two sources of heat, using the
outside temperature as parameter
to discriminate between spring
and autumn and winter.Actuator
F430/2 manages the switching ON
or OFF of the Boiler and changes
the valve state, while the Gateway
manages the Climaveneta Chiller.In
the example given here the Chiller
continues to work as long as the
outside temperature (measured
by the Climaveneta outside
probe) remains higher than a set
threshold value; below this value the
Combination boiler starts to work.
Using TiThermo set the Outside
Temperature (OT) value below which
the Boiler starts to work: for example
set 5°C.
When OT is higher than 5°C the
Chiller manages the system.When
OT is lower than 5°C the following
actions take place: Chiller OFF, Boiler
ON and valve open towards the
Boiler.
The Boiler continues to work until
OT rises above a value higher than
5°C. This selection is made to avoid
device state oscillation phenomena.
If for example 7°C is set as threshold
value, when OT is higher than 7°C the
following actions take place: Chiller
TiThermo: example of an application window, indispensable for programming
and setting the temperature thresholds and the automations.
ON, Boiler OFF, valve open towards
the Chiller.To sum up, the Chiller
continues to work until the OT drops
below 5°C; at this point the Boiler
starts to work.
It will stay on until the OT rises above
7°C, when the Chiller switches on
again.
NOTE: for the TiThermo software setting details
consult the documentation supplied with the product
itself.
< previous